ET25SWE0012 - PCM Enhanced Ceilings

Active
Project Name
PCM Enhanced Ceilings
Project Number
ET25SWE0012
Funding Entity
SWE
Market Sector
Other
Market Sector Other
Public and Commercial
TPM Category Priority 1
HVAC
TPM Technology Family Type 1
Commercial Scalable Thermal Storage
Distribution Report
Project Description

This project demonstrates the energy-saving benefits of phase change material (PCM) in drop ceilings to reduce cooling energy in California schools, where HVAC systems account for 50% of energy use (Energy Information Administration, 2018). Cooling dominates HVAC loads in warm classrooms due to high internal gains from dense student occupancy (Pistochini et al., 2022). PCM technology stores thermal energy by transitioning between solid and liquid phases at a designed temperature—71°F in this project—offering a passive, efficient way to reduce cooling loads.

PCM integrates well with HVAC systems equipped with outside air economizers. These systems, controlled by a Building Automation System (BAS), ventilate buildings during early morning hours to freeze the PCM. Based on data from PCM research, PCM can store 35–50 BTU/sf, reducing cooling loads by 3–4.3 ton-hours daily for a 1,000-sf classroom. With an average cooling energy intensity of 1 kWh/ton-hour, this equates to 300–430 kWh savings annually, or approximately 15–20% of the national average cooling energy use for classrooms (Energy Information Administration, 2018). PCM ceiling tiles seamlessly integrate with existing tiles, requiring no visual changes to classrooms.

Beyond energy savings, PCM offers co-benefits. Frozen PCM provides temporary cooling during HVAC outages or power failures. It also stabilizes surface temperatures, enhancing thermal comfort (Pistochini et al., 2024). Additionally, PCM installation can reduce noise transfer from rooftop HVAC units, addressing teacher complaints about noise interfering with learning (Outcault et al., 2022).

This project involves a field demonstration at a high school in Sunnyvale, CA, comparing classrooms with and without PCM. Three scenarios will be evaluated: (1) no PCM, no nighttime ventilation; (2) no PCM, with nighttime ventilation; and (3) PCM with nighttime ventilation to freeze the material. EnergyPlus models will be adapted and validated using field data (Pistochini et al., 2018, 2024) to quantify cooling energy reductions and load-shedding potential. Successful results could support statewide benefit projections in future projects.

The project addresses TPMs:

  • - HVAC: Commercial scalable thermal storage (medium): Building mass thermal storage: Performance validation
  • - Envelope: Thermal mass additions and improvements (medium): Thermal mass additions and improvements: Performance validation

    This project addresses the need for building mass thermal storage performance validation under the HVAC thermal storage research initiative. Field data will provide a case study and validate an EnergyPlus classroom model, which incorporates prior efforts on PCM performance validated with lab data (Pistochini et al., 2024). If successful, the tools can forecast statewide benefits in future projects.

The study will develop and demonstrate a simple, rule-based control strategy to freeze PCM using nighttime ventilation, a critical but often neglected factor in achieving HVAC energy savings. Field demonstrations will explore cost and control complexity barriers, aligning with identified challenges in thermal storage integration. By leveraging PCM integration with building automation systems, the project aims to validate scalable solutions, enable accurate savings estimates, and support future adoption. The results will contribute to broader PCM implementation in classrooms, supported by potential utility incentives and field-tested benefits.

Abstract

Phase change material (PCM) drop ceiling tiles are a non-invasive retrofit that have the potential to enhance building thermal energy storage, shift cooling loads, and reduce HVAC energy consumption. However, quantifying their performance in real-world environments is challenging due to operational variability in building mechanical systems. This study evaluated PCM ceiling tiles relative to conventional mineral fiber tiles via side-by-side field monitoring in four high school classrooms in California Climate Zone 3. To isolate the tiles' performance, the methodology incorporated standardized thermostat setpoints and deployed a custom nighttime ventilation pre-cooling algorithm for days with forecasted highs exceeding 70°F. The field study was supplemented with EnergyPlus simulation modeling to explore broader climate applicability and HVAC configuration impact. Empirical field data demonstrated a 25.6% HVAC energy reduction on the building's northside, likely partially attributed to duct leakage, while southern rooms showed no statistically significant field savings. Given the substantial operational variance, isolating PCM effects was partially dependent on EnergyPlus modeling, which indicated that the PCM retrofits independently account for up to 8.0% in energy reductions in northern configurations, with a 4.0% increase in energy use on the south side across the same timeframe, indicating significant impact from orientation and corresponding solar gains on PCM efficacy. Field measurements also confirmed statistically significant decreases in ceiling temperature fluctuations that may translate to improved occupant thermal comfort. These findings ultimately conclude that PCM ceiling tiles provide a potentially viable pathway for building decarbonization, yielding HVAC energy savings up to 8.0% depending on climate zone. However, the findings are limited to a single field study and simulation modeling of one building construction, and PCM performance may differ in buildings with other construction characteristics and operating conditions. Because installation costs mirror traditional materials, benefits of widespread adoption will depend on product pricing, lifespan, and local energy rates. When coupled with optimized climate selection and pre-cooling activation, PCM retrofits can offer a low-disruption solution for efficiency gains.