ET24SWG0004 - GAHP Performance Mapping with H2
This study aims to characterize the hydrogen fuel blending performance (up to 30% blend) of a Robur Gas Absorption Heat Pump (GAHP)-A unit to sufficiently populate model inputs in EnergyPlus. Gas Technology Institute (GTI) Energy will serve as a contractor for this study. They will develop a test plan including instrumentation, plumbing, and instrumentation diagram (P&ID) and testing tolerances and the commission the unit to carry out all equipment commissioning according to the manufacturer's rating conditions and laboratory testing. The testing will consist of both static performance mapping and transient performance mapping. At the completion of the testing, GTI will generate curve fits and implement them in the Energy Plus GAHP model.